Continuing Operation

This section explains functions for continuing or automatically restarting Inverter operation using speed
search even if an error occurs.

Restarting Automatically After Power Is Restored

Even if a temporary power loss occurs, you can perform estimated/current detection speed search using the
speed search function (b3-01) and restart the Inverter automatically after power is restored to continue motor
operation. To restart the Inverter after power has been restored, set L2-01 to 1 or 2. Make settings of L2-01 to
L2-05 and b3-01 for related details of restarting.
If L2-01 is set to 1:
when power is restored within the time set in L2-02, the Inverter will restart. If the time set in L2-02 is
exceeded, alarm UV1 (main circuit undervoltage) will be detected.
If L2-01 is set to 2:
when the main power supply is restored while the control power supply (i.e., power supply to the control
panel) is backed up, the Inverter will restart. Consequently, alarm UV1 (main circuit undervoltage) will not
be detected.
Related Constants
Name
Con-
stant
Display
Number
Momentary
power loss
detection
L2-01
瞬时停电动作选
Momentary
power loss ride-
thru time
L2-02
瞬时停电补偿时
Min. baseblock
time
L2-03
最小 BB 时间
Description
0: Disabled [main circuit
undervoltage (UV1)
detection]
1: Enabled [Restarted when the
power returns within the time
for L2-02. When L2-02 is
exceeded, main circuit
undervoltage (UV1) is
detected.]
2: Enabled while CPU is
operating. [Restarts when
power returns during control
operations. Does not detect
main circuit undervoltage
(UV1).]
Ridethrough time, when Momen-
tary Power Loss Selection (L2-
01) is set to 1, in units of seconds.
Sets the Inverter's minimum base-
block time in units of one second,
when the Inverter is restarted after
power loss ridethrough.
Sets the time to approximately 0.7
times the motor secondary circuit
time constant.
When an overcurrent or overvolt-
age occurs when starting a speed
search or DC injection braking,
increase the set values.
Control Methods
Change
Setting
Factory
during
V/f
Range
Setting
Opera-
V/f
with
tion
PG
0 to 2
0
No
A
A
0 to
0.1 s
No
A
A
25.5
*1
0.1 to
0.2 s
No
A
A
5.0
*1

Continuing Operation

MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vector
Vector
ter
tor
1
2
A
A
A
485H
A
A
A
486H
A
A
A
487H
63
6-