Setting User Constants
Here, the procedure is shown to change C1-01 (Acceleration Time 1) from 10 s to 20 s.
Table 3.4 Setting User Constants in Advanced Programming Mode
Step
Digital Operator Display
No.
1
2
3
4
5
6
7
8
9
10
11
12
Power supply turned ON.
MENU Key pressed to enter drive mode.
MENU Key pressed to enter quick programming mode.
MENU Key pressed to enter advanced programming mode.
DATA/ENTER pressed to access monitor display.
Increment or Decrement Key pressed to display C1-01 (Acceleration Time 1).
DATA/ENTER Key pressed to access setting display. The setting of C1-01
(10.00) is displayed.
Shift/RESET Key pressed to move the flashing digit to the right.
Increment Key pressed to change set value to 20.00 s.
DATA/ENTER Key pressed to enter the set data.
" 写入完毕 " is displayed for 1.0 s after the data setting has been confirmed
with the DATA/ENTER Key.
The monitor display for C1-01 returns.