Monitor Constants

This section explains the analog monitor and pulse monitor constants.

Using the Analog Monitor Constants

This section explains the analog monitor constants.
Related Constants
Con-
stant
Number
H4-01
H4-02
H4-03
H4-04
H4-05
H4-06
H4-07
-88
6
Name
Description
Display
Monitor selec-
Sets the number of the monitor
tion (terminal
item to be output (U1-
FM)
terminal FM.
4, 10 to 14, 25, 28, 34, 39, 40 can-
not be set. 29 to 31 and 41 are not
端子 FM 设定
used.
Gain (terminal
Sets the multi-function analog
FM)
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multiples
of 10 V.
端子 FM 增益
The maximum output from the
terminal is 10 V. A meter calibra-
tion function is available.
Bias (terminal
Sets the multi-function analog
FM)
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a per-
centage of 10 V.
端子 FM 偏置
The maximum output from the
terminal is 10 V. A meter calibra-
tion function is available.
Monitor selec-
Sets the number of the monitor
tion (terminal
item to be output (U1-
AM)
terminal AM.
4, 10 to 14, 25, 28, 34, 39, 40 can-
not be set. 29 to 31 and 41 are not
端子 AM 设定
used.
Gain (terminal
Set the voltage level gain for
AM)
multi-function analog output 2.
Set the number of multiples of 10
V to be output as the 100% output
for the monitor items. The maxi-
端子 AM 增益
mum output from the terminal is
10 V. A meter calibration function
is available.
Bias (terminal
Sets the multi-function analog
AM)
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a per-
centage of 10 V.
端子 AM 偏置
The maximum output from the
terminal is 10 V. A meter calibra-
tion function is available.
Analog output 1
Sets the signal output level for
signal level
multi-function output 1 (terminal
selection
FM)
0: 0 to +10 V output
AO1 信号电平
1: -10 to 10 V output
Change
Setting
Factory
during
Range
Setting
Opera-
tion
) from
1 to 45
2
No
0.00 to
1.00
Yes
2.50
-10.0
to
0.0%
Yes
+10.0
) from
1 to 45
3
No
0.00 to
0.50
Yes
2.50
-10.0
to
0.0%
Yes
+10.0
0 or 1
0
No
Control Methods
Open
Open
V/f
Flux
Loop
Loop
V/f
with
Vec-
Vector
Vector
PG
tor
1
2
A
A
A
A
A
Q
Q
Q
Q
Q
A
A
A
A
A
A
A
A
A
A
Q
Q
Q
Q
Q
A
A
A
A
A
A
A
A
A
A
MEMO
BUS
Regis-
ter
41DH
41EH
41FH
420H
421H
422H
423H