Output Terminal Functions - YASKAWA varispeed G7 CIMR-G7B series Instruction Manual

General purpose inverter (advanced vector control)
Table of Contents

Advertisement

Output Terminal Functions

The output terminal function, which sets the output methods by switching the functions of the multi-func-
tion output terminals (M1-M2, P1-PC, P2-PC, P3-C3, and P4-C4), is described here.
During Run (Setting: 0)
OFF
ON
During Run 2 (Setting: 37)
OFF
ON
These outputs can be used to indicate the Inverter's operating status.
Zero-speed (Setting: 1)
OFF
ON
Output frequency
Zero-speed output
-86
6
The Run Command is OFF and there is not output voltage.
The Run Command is ON or a voltage is being output.
The Inverter is not outputting a frequency. (Baseblock, DC injection braking, initial excitation, or
stopped)
The Inverter is outputting a frequency.
OFF
ON
Run Command
OFF
Baseblock command
Output frequency
OFF
ON
During run 1 output
OFF
During run 2 output
Fig 6.55 Timing Chart for "During RUN" Output
The output frequency is greater than the minimum output frequency (E1-09).
(With flux vector control, is greater than the zero-speed level (b2-01).)
The output frequency is less than the minimum output frequency (E1-09).
(With flux vector control, is less than the zero-speed level (b2-01).)
OFF
Fig 6.56 Timing Chart for Zero-speed
ON
ON
Minimum output frequency (E1-09)
(Zero speed level (b2-01) when flux vector control is
being used.)
ON