When constant H3-09 or H3-05 is set to D (frequency bias 2), the frequency equivalent to the terminal A2 or
A3 input voltage is added to A1 as a bias.

Operation Avoiding Resonance (Jump Frequency Function)

The jump frequency function operates the motor while avoiding resonance caused by characteristic frequen-
cies in the machinery.
This function is effective in creating a frequency reference dead band.
During constant-speed operation, operation within the jump frequency range is prohibited. Smooth operation
still used during acceleration and deceleration, i.e., jumps are not performed.
Related Constants
Name
Con-
stant
Display
Number
Jump fre-
Set the center values of the jump
quency 1
frequencies in Hz.
d3-01
This function is disabled by set-
禁止频率 1
ting the jump frequency to 0 Hz.
Always ensure that the following
Jump fre-
applies:
quency 2
d3-02
d3-01 ≥ d3-02 ≥ d3-03
禁止频率 2
Operation in the jump frequency
range is prohibited but during
Jump fre-
acceleration and deceleration,
quency 3
d3-03
speed changes smoothly without
jump.
禁止频率 3
Jump fre-
Sets the jump frequency band-
quency width
width in Hz.
d3-04
The jump frequency will be the
禁止频率幅度
jump frequency ± d3-04.
The relationship between the output frequency and the jump frequency reference is as follows:
Frequency reference
10%
Bias
0 V
Setting
Description
Range
0.0 to
400.0
0.0 to
Adjusting Frequency References
H3-02
Terminal A1 input voltage
10 V
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
0.0 Hz
No
A
A
0.0 Hz
No
A
A
0.0 Hz
No
A
A
1.0 Hz
No
A
A
20.0
MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vector
Vector
ter
tor
1
2
A
A
A
294H
A
A
A
295H
A
A
A
296H
A
A
A
297H
31
6-