Selecting the Number of PG (Encoder) Pulses

The setting for the number of PG pulses depends on the model of PG Speed Control Board being used. Set the
correct number for your model.
PG-A2/PG-B2
The maximum response frequency is 32,767 Hz.
Use a PG that outputs a maximum frequency of approximately 20 kHz for the rotational speed of the motor.
Motor speed at maximum frequency output (min
Some examples of PG output frequency (number of pulses) for the maximum frequency output are shown in
Table 2.21.
Motor's Maximum Speed (min
1800
1500
1200
900
Note 1. The motor speed at maximum frequency output is expressed as the sync rotation speed.
2. The PG power supply is 12 V.
3. A separate power supply is required if the PG power supply capacity is greater than 200 mA. (If momentary power loss must be handled, use a
backup capacitor or other method.)
−1
)
60
Table 2.21 PG Pulse Selection Examples
PG Rating
−1
)
(p/rev)
600
600
900
1200
PG power supply
Capacitor for momentary
power loss
Fig 2.30 PG-B2 Connection Example
Installing and Wiring Option Boards
× PG rating (p/rev) = 20,000 Hz
PG Output Frequency for Maximum Fre-
quency Output (Hz)
18,000
15,000
18,000
18,000
Signals
39
2-