EMC Directive

Varispeed G7-Series Inverters satisfy testing for conformance to the EMC Directive under the conditions
described in European Standard EN61800-3.
Installation Method
In order to ensure that the machinery or installation incorporating the Inverter conforms to the EMC Directive,
perform installation according to the method below.
Install a noise filter that conforms to European Standards on the input side. (Refer to Table 10.5 EMC
Noise Filters).
Use a shielded line or metal piping for wiring between the Inverter and Motor. Make the wiring as short as
possible.
To suppress harmonics, install a DC reactor in CIMR-G7B20P4, 20P7, 40P4, and 40P7 models. (Refer to
Table 10.6 DC Reactors for Suppressing Harmonics.)
R/L1, S/L2, T/L3
Inputs
Filter
Outputs
Wiring length:
40 cm max.
Metallic plate
Remove the paint on the ground side.
Fig 10.7 Installation Method for Filter and Inverter (CIMR-G7B20P4 to 2015, 40P4 to 4015)
PE
Remove the paint on the ground side.
Inverter
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3
Wiring length: 20 m max.