Motor Overload Protection
You can protect the motor from overload using the Inverter's built-in electronic thermal overload relay.
Related Constants
Name
Con-
stant
Display
Number
Motor rated
Sets the motor rated current in 1 A
current
units.
These set values will become the
reference values for motor protec-
E2-01
tion, torque limits and torque con-
电机额定电流
trol.
This constant is automatically set
during autotuning.
Motor 2 rated
Sets the motor rated current in 1 A
current
units.
These set values will become the
reference values for motor protec-
E4-01
tion, torque limits and torque con-
电机额定电流
trol.
This constant is automatically set
during autotuning.
Motor protec-
Sets whether the motor overload
tion selection
function is enabled or disabled at
electric thermal overload relay.
0: Disabled
1: General-purpose motor
2: Inverter motor protection
3: Vector motor protection
L1-01
In some applications when the
电机保护功能选
Inverter power supply is turned
择
off, the thermal value is reset, so
even if this constant is set to 1,
protection may not be effective.
When several motors are con-
nected to one Inverter, set to 0 and
ensure that each motor is installed
with a protection device.
Motor protec-
Sets the electric thermal detection
tion time con-
time in seconds units.
stant
Usually setting is not necessary.
The factory setting is 150% over-
L1-02
load for one minute.
When the motor's overload resis-
电机保护时间
tance is known, also set the over-
load resistance protection time for
when the motor is hot started.
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
Setting
Description
Range
0.32 to
6.40
*2
0.32
6.40
*3
protection
0 to 3
0.1 to
5.0
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
1.90 A
No
Q
Q
*1
to
1.90 A
No
A
A
*1
1
No
Q
Q
1.0
No
A
A
min
Machine Protection
MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vector
Vector
ter
tor
1
2
Q
Q
Q
30EH
A
A
A
321H
Q
Q
Q
480H
A
A
A
481H