Motor Overload Protection

You can protect the motor from overload using the Inverter's built-in electronic thermal overload relay.
Related Constants
Name
Con-
stant
Display
Number
Motor rated
Sets the motor rated current in 1 A
current
units.
These set values will become the
reference values for motor protec-
E2-01
tion, torque limits and torque con-
电机额定电流
trol.
This constant is automatically set
during autotuning.
Motor 2 rated
Sets the motor rated current in 1 A
current
units.
These set values will become the
reference values for motor protec-
E4-01
tion, torque limits and torque con-
电机额定电流
trol.
This constant is automatically set
during autotuning.
Motor protec-
Sets whether the motor overload
tion selection
function is enabled or disabled at
electric thermal overload relay.
0: Disabled
1: General-purpose motor
2: Inverter motor protection
3: Vector motor protection
L1-01
In some applications when the
电机保护功能选
Inverter power supply is turned
off, the thermal value is reset, so
even if this constant is set to 1,
protection may not be effective.
When several motors are con-
nected to one Inverter, set to 0 and
ensure that each motor is installed
with a protection device.
Motor protec-
Sets the electric thermal detection
tion time con-
time in seconds units.
stant
Usually setting is not necessary.
The factory setting is 150% over-
L1-02
load for one minute.
When the motor's overload resis-
电机保护时间
tance is known, also set the over-
load resistance protection time for
when the motor is hot started.
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
Setting
Description
Range
0.32 to
6.40
*2
0.32
6.40
*3
protection
0 to 3
0.1 to
5.0
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
1.90 A
No
Q
Q
*1
to
1.90 A
No
A
A
*1
1
No
Q
Q
1.0
No
A
A
min
Machine Protection
MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vector
Vector
ter
tor
1
2
Q
Q
Q
30EH
A
A
A
321H
Q
Q
Q
480H
A
A
A
481H
57
6-