Setting Motor Constants
In vector control method, the motor constants are set automatically using autotuning. If autotuning does not
complete normally, set them manually.
Related Constants
Name
Con-
stant
Display
Number
Motor rated
Sets the motor rated current in 1 A
current
units.
These set values will become the
reference values for motor protec-
E2-01
tion, torque limits and torque con-
电机额定电流
trol.
This constant is automatically set
during autotuning.
Motor rated slip Sets the motor rated slip in Hz
units.
These set values will become the
E2-02
reference values for slip compen-
电机额定滑差
sation.
This constant is automatically set
during autotuning.
Motor no-load
Sets the motor no-load current in
current
1 A units.
E2-03
This constant is automatically set
空载电流
during autotuning.
Number of
Sets the number of motor poles.
motor poles
E2-04
This constant is automatically set
during autotuning.
电机极数
Motor line-to-
Sets the motor phase-to-phase
resistance in Ω units.
line resistance
E2-05
This constant is automatically set
线间电阻
during autotuning.
Motor leak
Sets the voltage drop due to motor
inductance
leakage inductance as a percent-
E2-06
age of the motor rated voltage.
This constant is automatically set
电机漏电感
during autotuning.
Motor iron sat-
Sets the motor iron saturation
uration coeffi-
coefficient at 50% of magnetic
E2-07
cient 1
flux.
This constant is automatically set
饱和系数 1
during rotational autotuning.
Motor iron sat-
Sets the motor iron saturation
uration coeffi-
coefficient at 75% of magnetic
E2-08
cient 2
flux.
This constant is automatically set
饱和系数 2
during rotational autotuning.
Motor iron loss
for torque com-
E2-10
Sets motor iron loss in W units.
pensation
铁损
Setting
Factory
Description
Range
0.32 to
1.90 A
6.40
*2
0.00 to
20.00
0.00 to
1.20 A
1.89
*3
2 to 48
0.000
to
65.000
0.0 to
18.2%
40.0
0.00 to
0.50
0.00 to
0.75
0 to
65535
Control Methods
Change
Open
during
V/f
Loop
Setting
Opera-
V/f
with
Vector
tion
PG
1
No
Q
Q
Q
*1
2.90
No
A
A
A
Hz
*1
No
A
A
A
*1
4
No
No
Q
No
poles
9.842
Ω
No
A
A
A
*1
No
No
No
A
*1
0.50
No
No
No
A
0.75
No
No
No
A
14 W
No
A
A
No
*1
Individual Functions
MEMO
Open
BUS
Flux
Loop
Regis-
Vec-
Vector
ter
tor
2
Q
Q
30EH
A
A
30FH
A
A
310H
Q
Q
311H
A
A
312H
A
A
313H
A
A
314H
A
A
315H
No
No
317H
117
6-