Table 4.3 Constant Settings before Autotuning (Continued)
Name
Con-
stant
Num-
Display
ber
Motor base
speed
Set the base speed of the motor
T1-07
−1
in min
电机额定速
Number of
PG pulses
Set the number of pulses for the
when turn-
PG (pulse generator or
ing
T1-08
encoder). Set the number of
pulses per motor revolution
without a multiplication factor.
PG 脉冲数
Motor no-
Set the current value recorded
load cur-
in the motor's test results for a
rent
motor without a load.
T1-09
Displayed only when Stationary
autotuning 2 is selected (T1-01
电机的空载
电流
= 4).
* 1. Not normally displayed. Displayed only when a motor switch command is set for a multi-function digital input (one of H1-01 to H1-10 set to 16).
* 2. The factory setting depends on the Inverter capacity. Values are given for a 200 V Class, 0.4 kW Inverter.
* 3. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for a 0.4 kW is given.
* 4. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.
* 5. For fixed output motors, set the base speed value.
* 6. For Inverter motors or for specialized vector motors, the voltage or frequency may be lower than for general-purpose motors. Always confirm the infor-
mation on the nameplate or in test reports. If the no-load values are known, input the no-load voltage in T1-03 and the no-load current in T1-05 to
ensure accuracy.
* 7. The settings that will ensure stable vector control are between 50% and 100% of the Inverter rating.
* 8. Refer to Chapter 8 Procedure for Adjusting Constants after Replacement of Control Board (Page 8-3) for the details of setting 3 (Shipping adjustment).
* 9. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of
E2-01.
Refer to page 3-15 for Digital Operator displays during autotuning.
Precautions for Precision Settings
Settings for autotuning are different when performing autotuning using motor test reports or design data. Use
the following table as reference.
Operator Display
T1-03
T1-05
Setting
Display
Range
0 to 24000
*5
.
0 to 60000
0.00 to 1.89
*9
Simple Setting
Motor rated voltage
Motor base frequency
Trial Operation Procedures
Data Displays during Autotuning
Open
Factory
V/f
-loop
Setting
V/f
with
Vec-
PG
tor 1
1450
-
-
Yes
−1
min
600
-
Yes
-
1.20A
No
No
Yes
*2
Precision Setting
Voltage under no-load con-
ditions at motor rated speed
Frequency under no-load
conditions at rated speed
Open
Flux
-loop
Vec-
Vec-
tor
tor 2
Yes
Yes
Yes
-
Yes
Yes
15
4-