TableApp.45 Special relay not supported in the Universal model QCPU and measures (Continued)
Number
Name/Description
SM280
CC-Link error
Communication reserved time delay
SM315
enable/disable flag
Operation mode for low-speed
SM330
execution type program
Normal SFC program execution
SM331
status
Program execution management
SM332
SFC program execution status
SM390
Access execution flag
ON for only 1 scan after RUN of low-
SM404
speed execution type programs
Off for only 1 scan after RUN of low-
SM405
speed execution type programs
User timing clock No.5 (for low-
SM430
speed execution type programs)
User timing clock No.6 (for low-
SM431
speed execution type programs)
User timing clock No.7 (for low-
SM432
speed execution type programs)
User timing clock No.8 (for low-
SM433
speed execution type programs)
User timing clock No.9 (for low-
SM434
speed execution type programs)
Low-speed execution type program
SM510
executing flag
SM551
Module service interval time read
SM580
Program to program I/O refresh
SM660
Boot operation
Memory card file register access
SM672
range flag
SM710
CHK instruction priority flag
XCALL instruction execution
SM734
condition specification
SFC comment readout instruction in-
SM735
execution flag
App - 65
Replace the relay with the I/O signals (Xn0, Xn1, and XnF) of the mounted CC-Link
module.
Set a service processing time value in the PLC system tab of the PLC parameter dia-
log box.
The Universal model QCPU does not support low-speed execution type programs.
Delete the corresponding sections.
The Universal model QCPU supports only normal SFC programs. Delete SM331 and
SM332, which are used as interlocks, or replace them with SM321.
Modify the program that Module ready signal (Xn) is used as an interlock, according
to sample programs described in the manual for each module.
The Universal model QCPU does not support low-speed execution type programs.
Delete the corresponding sections or replace them with the special relays for scan
execution type programs (SM402 and SM403).
The Universal model QCPU does not support low-speed execution type programs.
Delete the corresponding sections or replace them with the special relays for scan
execution type programs (SM420 and SM424).
The Universal model QCPU does not support low-speed execution type programs.
Delete the corresponding sections.
The Universal model QCPU does not support the service interval measurement
function. Delete the corresponding sections.
Perform I/O refresh at the start or end of each program with the RFS or COM instruc-
tion.
Move files with a boot setting (from the standard ROM or a memory card to the pro-
gram memory) to the program memory.
When outside the range of the file register in the memory card is accessed, the
Universal model QCPU detects "OPERATION ERROR" (error code: 4101).
Programming for detecting errors using this special realy is not necessary. Delete
the corresponding sections.
The Universal model QCPU does not support the CHK instruction. For the replacing
method of the CHK instruction, refer to Appendix 3.3.
The Universal model QCPU executes the XCALL instruction on the rising edge of
execution condition as well. There is no application for this special relay. Delete the
corresponding sections.
The Universal model QCPU does not support the following instructions:
• SFC step comment readout instruction (S(P).SFCSCOMR)
• SFC transition condition comment readout instruction (S(P).SFCTCOMR)
Delete the corresponding sections.
Measures
(To the next page)