Appendix 3.1.2 Replacing High Performance model QCPU with Universal
model QCPU
(1)
System configuration
TableApp.9 Precautions for replacement and replacement methods (System configuration)
Item
Use of AnS/A series
AnS/A series modules are not supported.
module
GOT
GOT900 series cannot be connected.
Applicable USB cables are different.
• High Performance model QCPU
Programming tool
... A-B type
connection
• Universal model QCPU
... A-miniB type
Applicable device and
Devices and softwares compatible with
software
the Universal model QCPU must be used.
To configure a multiple CPU system, CPU
modules compatible with the Universal
model QCPU must be used.
Multiple CPU system
In a multiple CPU system using the
Motion CPU, an existing auto refresh area
and user setting area cannot be used for
data communication with the Motion CPU.
In a redundant power supply system
using the Q38RB redundant power supply
main base unit and the Q68RB redundant
power supply extension base unit, the
Redundant power
status of the power supply module cannot
*1
supply system
be stored in the special relay and special
register (SM1780 to SM1783/SD1780 to
SD1783). The status cannot be displayed
on the system monitor screen.
The simple dual-structured network
MELSECNET/H
function is not supported.
*1: The serial number (first five digits) of the applicable module (Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, and
Q26UDHCPU) must be "10041" or earlier.
Precautions
Use Q series modules.
Use GOT1000 series.
Use USB cables of A-miniB type. Or, use
USB conversion adapters of B-miniB
type.
Devices need to be replaced for the
compatibility with the Universal model
QCPU and software need to be upgraded
for the communication with the Universal
model QCPU are described in Appendix
3.2.
CPU modules compatible with the
Universal model QCPU are described in
Appendix 3.2.
For data communication with the Motion
CPU, use an auto refresh area and user
setting area in the multiple CPU high-
speed transmission area.
Check the status of the power supply
module by the LED on the front of the
module.
Replacement method
---
APPENDICES
Reference
---
---
---
APPEN-
Appendix 3.2
Appendix 3.2
Chapter 4 in the QCPU
User's Manual (Multiple
CPU System)
Section 5.3 in the
QCPU User's Manual
(Hardware Design,
Maintenance and
Inspection)
Section 7.7 in the Q
Corresponding
MELSECNET/H
Network System
Reference Manual (PLC
to PLC network)
App - 12
1
2
3
DIX
6
7
8