(4) Executing method
There are three methods for performing the remote RUN/STOP operation.
• Using a RUN contact
• By GX Developer or an external device using the MC protocol
• With link dedicated instructions of the CC-Link IE controller network module or MELSECNET/H
module
(a) Using a RUN contact
Set a RUN contact in the PLC system tab of the PLC parameter dialog box.
The settable device range is X0 to 1FFF.
The remote RUN/STOP operation can be performed by turning on/off the set RUN contact.
• When the RUN contact is turned off, the CPU module status changes to RUN.
• When the RUN contact is turned on, the CPU module status changes to STOP.
(b) By GX Developer or an external device using the MC protocol
Select [Online]
To perform the remote RUN/STOP operation from an external device, use the MC protocol
command.
Q Corresponding MELSEC Communication Protocol Reference Manual
GX Developer
or
External device
6 - 18
Step 0
OFF
RUN contact
RUN
RUN/STOP status
Figure 6.15 Remote RUN/STOP using a RUN contact
[Remote operation] in GX Developer.
Step 0
Remote STOP
OFF
command
OFF
Remote RUN
command
RUN
RUN/STOP status
Figure 6.16 Remote RUN/STOP by GX Developer or an external device
Step 0
END
ON
STOP
STOP status
END
ON
STOP
STOP status
END
0
Step 0
END
0
ON