6.9

H/W Error Time PLC Operation Mode Setting

(1) Definition
This function determines the program operation mode (stop or continue) of the CPU module when a
hardware error occurs in an intelligent function module or interrupt module.
(2) H/W error time PLC operation mode setting
Set the H/W error time PLC operation mode in the I/O assignment tab of the PLC parameter dialog
box.
Make I/O assignment for the target module
1)
Click the
2)
3) On the screen opened, select "Stop" or "Continue". (Default: "Stop")
1) Make I/O assignment.
(3) Precautions
The H/W error time PLC operation setting will be enabled when:
• the CPU module is powered off and then on, or
• the CPU module is reset.
button.
Detailed setting
2) Click the Detailed setting button.
Figure 6.24 H/W error time PLC operation setting
.
3) Select "Stop" or "Continue" for
the H/W error time PLC operation mode.
CHAPTER6 FUNCTIONS
6 - 29