Mitsubishi Electric melsec q00ujcpu User Manual page 337

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

Item
*1
Online module change
All CPUs
can read all
inputs
I/O sharing when
using Multiple CPUs
All CPUs
can read all
outputs
CPU specific send
Multiple
range
CPU high
speed
transmiss
ion area
Auto
*1
setting
Refresh
refresh
setting
setting
Communication area setting
(refresh setting)
*1: Not available for the Q00UCPU, Q01UCPU, and Q02UCPU.
*2: SM, SD, SB, and SW are valid only when they are selected as send devices.
8 - 17
Table8.12 Multiple CPU setting list (continued)
Parameter
Description
No.
Enable or disable the online
module change in the multiple
CPU system. (When enabled,
E006
H
the CPU module cannot read
the I/O data outside the
specified group.)
Select whether to read the
input data of the input modules
or intelligent function modules
controlled by another CPU.
0E04
H
Select whether to read the
output data of the output
modules controlled by another
CPU.
Set the size of the multiple
CPU high-speed transmission
E008
area that is assigned to each
H
CPU module of the multiple
CPU system.
Set an area range for data
communication performed with
E009
H
the auto refresh function in the
E00A
H
user area of the multiple CPU
high-speed transmission area.
In the multiple CPU system,
data are transferred by auto
E002
refresh among respective CPU
H
E003
modules.
H
Set the devices to be written or
read and their points.
Setting range
Selected/deselected
Deselected
Selected/deselected
Deselected
Selected/deselected
Deselected
Simple setting:
0 to 12K (in increments of 1K
points)
3K points
Advanced setting:
0 to 16K (in increments of
0.5K points)
*2
Available devices
:
X, Y, M, L, B, D, W, R, ZR,
SM, SD, SB, and SW
[Set starting devices for each
CPU]
Deselected
Selected/deselected
[CPU specific send range]
0 to 2048 points (in
increments of 2 points) per
CPU
Up to 8K points (8192 points)
per system
[PLC side device]
B, M, Y, D, W, R, or ZR
Occupies the device of the
Blank
points set for the send range
and starting from the
specified device number.
• One point in the send
range equals 16 points in
B, M, or Y.
• One point in the send
range equals one point in
D, W, R, or ZR.
Default
Reference
QQCPU Userís
-
Manual (Multiple
CPU System)

Advertisement

Table of Contents
loading

Table of Contents