(3) Limitation on the number of parameter settings
Limitations are placed on the number of parameters (initial setting and auto refresh setting) set in GX
Configurator.
When multiple intelligent function modules are mounted, make setting in GX Configurator so that the number of
parameter settings for all intelligent function modules may not exceed the limitation shown in Table7.2.
Q00UJCPU, Q00UCPU, Q01UCPU
Q02UCPU
Q03UDCPU, Q04UDHCPU, Q06UDHCPU,
Q10UDHCPU, Q13UDHCPU, Q20UDHCPU, Q26UDHCPU,
Q03UDECPU, Q04UDEHCPU, Q06UDEHCPU,
Q10UDEHCPU, Q13UDEHCPU, Q20UDEHCPU, Q26UDEHCPU
One line in the Auto refresh screen is counted as one parameter setting.
Remark
For details of GX Configurator, refer to the manual for the intelligent function module used.
7 - 4
Table7.2 Number of parameters set in GX Configurator
CPU module
Figure 7.3 Counting the number of parameter settings
Number of parameter settings
Initial setting
512
2048
4096
This one line is counted as one
parameter setting.
Blanks are not counted.
Add the number of lines on
this screen to those of other
intelligent function modules.
Auto refresh setting
256
1024
2048