Mitsubishi Electric melsec q00ujcpu User Manual page 134

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

(4) Precautions
(a) Setting the communication time check period in GX Developer
Since writing a file to the Flash card takes time, set "Check at communication time" in GX Developer to 60
seconds or longer.
If the set time is short, GX Developer may time out.
(b) Writing a file from GX Developer in another station via CC-Link
Since writing a file to the Flash card takes time, make the CPU monitoring time setting (SW000A) of CC-Link to
60 seconds or longer.
(The default value of 90 seconds can be used.)
GX Developer in another station
Figure 5.19 Writing a file from GX Developer in another station(via CC-Link)
Remark
For settings of the communication time check period and CPU monitoring time, refer to the following.
GX Developer Version8 Operating Manual
CHAPTER5 MEMORIES AND FILES USED FOR CPU MODULE
Figure 5.18 Check at communication time setting
CPU module that writes
files to the Flash card
1
2
3
4
5
6
7
8
5 - 21

Advertisement

Table of Contents
loading