Mitsubishi Electric melsec q00ujcpu User Manual page 332

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

(9) I/O assignment
The mounting status of each module in the system is set.
Parameter
Item
No.
Type
I/O
Assignme
0400
Model name
nt
Points
Start XY
Base model
name
Power model
name
Base
0401
setting
Extension
cable
Slots
Figure 8.9 I/O assignment
Table8.9 I/O assignment setting list
Description
Set the type of the mounted module.
Set the model name of the mounted
H
module. (Entered at user's discretion.
Do not use the one for the CPU
module.)
Set the number of points assigned to
each slot.
Set the start I/O number of each slot.
Set the model name of the main base
unit or extension base unit. (Entered at
user's discretion. Do not use the one
for the CPU module.)
Set the model name of the power
supply module on the main base unit
or extension base unit. (Entered at
user's discretion. Do not use the one
H
for the CPU module.)
Set the extension cable name.
(Entered at user's discretion. Do not
use the one for the CPU module.)
Set the number of slots of the main
base unit or extension base unit.
This setting must be done for all base
units.
Setting range
• CPU No.2 to No.4: No.n/Empty (Set
"CPU (Empty)" for the slot where no
CPU module is mounted.)
• Empty, Input, Hi input, Output,
Intelli., I/O mix, or Interrupt
Up to 16 characters
0, 16, 32, 48, 64, 128, 256, 512, or
1024 points
0
to FF0
H
H
Up to 16 characters
Up to 16 characters
Up to 16 characters
2, 3, 5, 8, 10, or 12
CHAPTER8 PARAMETERS
Default
Reference
Section
Blank
4.2.2
Section
Blank
4.1.2
(To the next page)
8 - 12
1
2
3
4
5
6
7
8