Mitsubishi Electric melsec q00ujcpu User Manual page 492

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

Number
Name
SM1760
SM1761
SM1762
SM1763
SM1764
SM1765
SM1766
OFF : Transmission
SM1767
Transfer trigger
completion flag
SM1768
ON : Transmission end
SM1769
SM1770
SM1771
SM1772
SM1773
SM1774
SM1775
(15) Redundant power supply module information
Number
Name
OFF : No redundant power
Power supply off
SM1780
detection flag
ON : Redundant power
OFF : No faulty redundant
Power supply failure
SM1781
detection flag
ON : Faulty redundant
Momentary power
failure detection flag
SM1782
*1
for power supply 1
OFF : No momentary power
ON : Momentary power
Momentary power
failure detection flag
SM1783
*1
for power supply 2
*1: The "power supply 1" indicates the redundant power supply module mounted on the POWER 1 slot of the redundant base unit (Q38RB/Q68RB/Q65WRB).
The "power supply 2" indicates the redundant power supply module mounted on the POWER 2 slot of the redundant base unit (Q38RB/Q68RB/Q65WRB).
*2: The module whose first 5 digits of serial No. is "04012" or later.
However, for the multiple CPU system configuration, this applies to all CPU modules whose first 5 digits of serial No. are "07032" or later.
*3: The module whose first 5 digits of serial No. is "10042" or later.
Table12.15 Special relay
Meaning
SM1760
Block 49
SM1761
Block 50
SM1762
Block 51
SM1763
Block 52
SM1764
Block 53
SM1765
Block 54
SM1766
Block 55
SM1767
Block 56
uncompleted
SM1768
Block 57
SM1769
Block 58
SM1770
Block 59
SM1771
Block 60
SM1772
Block 61
SM1773
Block 62
SM1774
Block 63
SM1775
Block 64
Table12.16 Special relay
Meaning
• Turns ON when one or more redundant power
supply module with
supply modules with input power OFF are detected.
input power OFF
• Turns on if any of SD1780 bits is on.
detected
• Turns off if all bits of SD1780 are off.
• Turns OFF when the main base unit is not the
supply module with
redundant main base unit (Q38RB).
input power OFF
• When the multiple CPU system is configured, the
detected
flags are stored only to the CPU No.1.
• Turns ON when one or more faulty redundant power
supply modules are detected.
power supply module
• Turns on if any of SD1781 bits is on.
detected
• Turns off if all bits of SD1781 are off.
• Turns OFF when the main base unit is not the
power supply module
redundant main base unit (Q38RB).
detected
• When the multiple CPU system is configured, the
flags are stored only to the CPU No.1.
• Turns ON when a momentary power failure of the
input power supply to the power supply 1 or 2 is
detected one or more times. After turning ON,
remains ON even if the power supply recovers from
the momentary power failure.
• Turns OFF the flag (SM1782, SM1783) of the power
failure detected
supply 1/2 when the CPU module starts.
• When the input power to one of the redundant power
failure detected
supply modules turns OFF the corresponding flag
turns OFF.
• Turns OFF when the main base unit is not the
redundant main base unit (Q38RB).
• When the multiple CPU system is configured, the
flags are stored only to the CPU No.1.
CHAPTER12 SPECIAL RELAY LIST AND SPECIAL REGISTER LIST
Explanation
(When Set)
Turns ON only during one
scan when the transmission
S (status change)
of the corresponding block is
completed.
Explanation
(When Set)
S (Each END)
S (Each END)
S (Each END)
Corres-
ponding
Set by
Corresponding
ACPU
CPU
M9
New
QnPRH
Corres-
Set by
ponding
Corresponding
ACPU
CPU
M9
Qn(H)
QnPH
New
QnPRH
QnU
12 - 26
1
2
3
12
6
7
8
*2
*2
*3