Install and Cable the Cabinets
AC Power and Ground

CMC Cabinet Power Switch

!
CAUTION:
The latch acts as the DC power switch and only removes DC power from
the cabinet, not AC power. To remove AC power, pull the AC power cord
from the appliance inlet. See
Figure Notes
1. Latch
Figure 1-9. CMC Power Supply

Connect Cabinet Grounds and Other Grounds

The following additional grounding requirements must be met:
The approved ground wire must be green, 6 AWG (#40) (16 mm
copper, stranded wire (this is in addition to the ground wire in the AC
power cord)