n Models
Refer to "Models" and "Events" under "Scheduler -
Timers".

Options

This page will allow you to setup the options that determine
the operating mode of the system.
Disable Tamper Memory Reset with User code
If this option is enabled, only the Installer Codes will be
able to delete the Zone, Partition and Control Panel
Tamper memories.
Maintain Zone Test Attribute If this option is en -
abled, any Alarms generated by Zones in Test status
will be recorded in the Events log, also when the Parti -
tion is Disarmed.
Enable dynamic battery test timeout after mains restoral
After providing power during a Mains blackout, the bat -
tery will be quite low, and therefore, unable to meet the
Dynamic Battery Test requirements (refer to "Power
supply connection" under "Installation"). If this option is
enabled, the Dynamic Battery Test will restart 5 hours
after Mains restoral (instead of immediately) thus allow -
ing the battery to recharge.
Disable Alarm Memory Reset With Installer Code
If this option is enabled, only enabled User Codes will
be able to delete Alarm memories.
LEDs OFF on Readers If this option is enabled, the
Reader LEDs will not signal the system status (all LEDs
OFF) until a valid Key/Card is used at the Reader.
+
The LEDs of Readers which have the M option En-
abled (refer to "Readers" under "Enrolling"), will al-
ways show the status of their associated events,
regardless of the status of the LEDs OFF on
Readers option.
Figure 48 Options page
74
Bypass Tamper on Zone If this option is enabled, by -
passed Zones will not generate Tamper Alarms.
Disable Arming on Battery Trouble If this option is
enabled, Arming requests will be denied when any of
the following events is in progress:
Ø Warning low battery
Ø Warning power trouble
Ø Warning low battery on Power station
Ø Warning power trouble on Power station
Lock Installer Code If this option is enabled, restoral
of the default settings WILL NOT default the PIN of
Code no. 200 (MASTER Installer Code).
Disable Arming with Partition Alarm If this option is
enabled, Arm commands from Keypads or Readers will
not be carried out if the system detects Partitions in
alarm status.
+
This option does not apply to Arming operations
done via a Command zone, Timer, remote Tele-
phone or computer.
Enable Automatic Update of
Standard Time/Summer Time If this option is en-
abled, the Control Panel will manage the Daylight
Saving Time changeover automatically, as follows:
Ø the Clock will be put forward 1 hour at 2 am on the
last Sunday in March;
Ø the Clock will be put back 1 hour at 3:00 am on the
last Sunday in October.
The system will signal Automatic Changeover by:
Ø generating the
Standard time/Summer time
changed event;
Ø switching ON the G LED.