CB FALCON MODBUS COMMUNICATION
Table 10. Falcon alert codes
80
Fan pulses per revolution was invalid
81
Fan PWM frequency was invalid
82-83
RESERVED
84
Lead Lag CH 4-20mA water temperature setting was
invalid
85
No Lead Lag add stage error threshold was
configured
86
No Lead Lag add stage detection time was
configured
87
No Lead Lag drop stage error threshold was
configured
88
No Lead Lag drop stage detection time was
configured
89
RESERVED
90
Modulation output type was invalid
91
Firing rate control parameter was invalid
92
Forced rate was out of range vs. min/max
modulation
93
Forced rate was invalid, % vs. RPM
94
Slow start ramp value was invalid
95
Slow start degrees value was invalid
96
Slow start was ended due to outlet sensor fault
97
Slow start was end due to reference setpoint fault
98
CH max modulation rate was invalid, % vs. RPM
99
CH max modulation rate was > absolute max rate
100
CH modulation range (max minus min) was too
small (< 4% or 40 RPM)
101
DHW max modulation rate was invalid, % vs. RPM
102
DHW max modulation rate was > absolute max rate
103
DHW modulation range (max minus min) was too
small (< 4% or 40 RPM)
104
Min modulation rate was < absolute min rate
105
Min modulation rate was invalid, % vs. RPM
106
Manual rate was invalid, % vs. RPM
107
Slow start enabled, but forced rate was invalid
108
Analog output hysteresis was invalid
109
Analog modulation output type was invalid
110
IAS open rate differential was invalid
111
IAS open step rate was invalid
112
Mix max modulation rate was invalid, % vs. RPM
113
Mix max modulation rate was > absolute max or <
absolute min rates
114
Mix modulation range (max minus min) was too
small (< 4% or 40 RPM)
115
Fan was limited to its minimum duty cycle
116
Manual rate was > CH max modulation rate
117
Manual rate was > DHW max modulation rate
118
Manual rate was < min modulation rate
119
Manual rate in Standby was > absolute max rate
120
Modulation commanded rate was > CH max
modulation rate
Table 10. Falcon alert codes
121
Modulation commanded rate was > DHW max
modulation rate
122
Modulation commanded rate was < min modulation
rate
123
Modulation rate was limited due to Outlet limit
124
Modulation rate was limited due to Delta-T limit
125
Modulation rate was limited due to Stack limit
126
Modulation rate was limited due to anticondensation
127
Fan speed out of range in RUN
128
Modulation rate was limited due to IAS was open
129
Slow start ramp setting of zero will result in no
modulation rate change
130
No forced rate was configured for slow start ramp
131
CH demand source was invalid
132
CH P-gain was invalid
133
CH I-gain was invalid
134
CH D-gain was invalid
135
CH OFF hysteresis was invalid
136
CH ON hysteresis was invalid
137
CH sensor type was invalid
138
CH hysteresis step time was invalid
139
CH remote control parameter was invalid
140
CH ODR not allowed with remote control
141
Steam P-gain was invalid
142
Steam I-gain was invalid
143
Steam D-gain was invalid
144
Steam OFF hysteresis was invalid
145
Steam ON hysteresis was invalid
146
CH control was suspended due to fault
147
CH header temperature was invalid
148
CH Outlet temperature was invalid
149
CH steam pressure was invalid
150
Steam setpoint source parameter was invalid
151
Minimum water temperature parameter was greater
than setpoint
152
Minimum water temperature parameter was greater
than time of day setpoint
153
Minimum pressure parameter was greater than
setpoint
154
Minimum pressure parameter was greater than time
of day setpoint
155
CH modulation rate source parameter was invalid
156
Steam modulation rate source parameter was invalid
157
DHW demand source was invalid
158
DHW P-gain was invalid
159
DHW I-gain was invalid
160
DHW D-gain was invalid
161
DHW OFF hysteresis was invalid
162
DHW ON hysteresis was invalid
163
DHW hysteresis step time was invalid