Dhw High Limit (Hydronic Control); Limits And Rate Override: Outlet High Limit - CleaverBrooks CFC Operation, Service & Parts Manual

Condensing boiler
Table of Contents

Advertisement

Table 23. Limits and Rate Override: Slow Start Limit Parameters. (Continued)
Parameter
CH slow start enable
DHW slow start enable
Slow start setpoint
Slow start ramp

DHW High Limit (Hydronic Control)

If DHW high limit enable is enabled then whenever the DHW high limit has been reached the DHW pump will be forced off. It will
remain off until the DHW input temperature is lower than the DHW high limit temperature minus 5°F. The DHW high limit pump
inhibit function is not a safety function.
Parameter
DHW high limit enable
DHW high limit setpoint
DHW high limit response
Enable, Disable
This parameter enables or disables the slow start limit function for CH and LL demand
sources. It uses the CH forced rate parameter as the starting point for the slow start. If the
forced rate parameter is invalid or zero and slow start is enabled, then the slow start function
does not occur and an alert is issued.
Enable, Disable
This parameter enables or disables the slow start limit function for DHW demand source. It
uses the DHW forced rate parameter as the starting point for the slow start. If this forced rate
parameter is invalid or zero and slow start is enabled, then the slow start function does not
occur and an alert is issued.
Degrees or None
If slow start limiting is enabled and the outlet temperature is less than the temperature
provided by subtracting this number of degrees from the setpoint, then slow start rate limiting
is effective. Whenever the outlet temperature is above this value, slow start limiting has no
effect.
RPM or % Per Minute
When slow start limiting is effective, the modulation rate will increase no more than the
amount per minute given by this parameter.
Although provided as a per-minute value, the Falcon will calculate and apply this as a
stepped function using a step duration of 10 seconds.
Table 24. Limits and Rate Override: Outlet High Limit.
Enable, Disable
This parameter enables or disables the DHW high limit function. It must be disabled when the
DHW input is used as a switch to indicate DHW demand.
If set to "Enable," the DHW connector type must be 10K dual safety NTC.
Degrees or None
If DHW high limit enable is enabled and the DHW temperature reaches the value given by
this parameter, then a response will occur.
Lockout, Recycle & Hold
This parameter selects the response.
If lockout is selected then the burner control locks out.
If Recycle & Hold is selected then the burner control recycles and holds until the DHW
temperature falls below the DHW high limit temperature minus 5°F.
Comment
Comment