Central Heat Parameters (Hydronic Control Only); System Identification Information - CleaverBrooks CFC Operation, Service & Parts Manual

Condensing boiler
Table of Contents

Advertisement

WARNING
Explosion Hazard.
Improper configuration can cause fuel buildup and
explosion.
Improper user operation may result in PROPERTY
LOSS, PHYSICAL INJURY or DEATH.
The OI Display used to change parameters, must be
attempted by only experienced and/or licensed
burner/boiler operators and mechanics.
Fig. 28. System identification and access configuration
(Hydronic Screen Shown).
Table 5 displays System Identification and Access
parameters.
Table 5. System Identification and Access Parameters.
Parameter
Boiler Name
Name to identify boiler (up to 20
characters)
Installation
Notes regarding installation (up to 20
characters)
Installer password
Change installer password setting
OEM password
Change OEM password setting
Factory Data
OEM name to associate with boiler
(up to 20 characters)
When the burner name is changed, the name is saved in the
Falcon and displayed in the title of all pages that
zoom into the control.
Default installer password is "9220".
CB-8462
Comment
14
Table 6. System Identification Information.
Status
Product Type
Type of product that the burner is
OS Number
Model number associated with burner
Software Version
Version of software running in the
Falcon
Date Code
Date when Falcon was
assembled
Application Revision Version of application data in the
Falcon
Safety Revision
Revision of safety data in the Falcon
Central Heat Parameters
(Hydronic Control Only)
Table 7 displays Central Heat Hydronic Control configuration
parameters.
Fig. 29. Central Heat hydronic configuration.
Table 7. Central Heat Hydronic
Configuration Parameters.
Parameter
CH enable
Disable or Enable Central Heating
Loop
Demand switch
Sensor for Central Heat demand:
Sensor only
Sensor & STAT terminal
Sensor & Remote Stat
LCI & Sensor
Outdoor reset
Enabled
Disabled
CH has priority over
Yes, No, Cancel
Lead Lag
Setpoint source
Local
S2 (J8-6) 4-20mA
Setpoint
Setpoint for normal Central Heat
modulation:
-40 °F to 266 °F (-40 °C to 130 °C)
Comment
Comment

Advertisement

Table of Contents
loading