CleaverBrooks CFC Operation, Service & Parts Manual page 241

Condensing boiler
Table of Contents

Advertisement

Table 48. Example of a Completed Device Parameter Worksheet. (Continued)
Parameter Name
CH P gain
CH I gain
CH D gain
CH hysteresis step time
Ignition source
BLR HSI function
Igniter on during
Pilot type
Flame sensor type
Purge rate proving
Lightoff rate proving
Prepurge time
Preignition time
PFEP
MFEP
Run stabilization time
Postpurge time
Interlock start check enable
Interlock open response
Ignite failure response
Ignite failure retries
Ignite failure delay
MFEP flame failure response Read Only
Run flame failure response
Pilot test hold
NTC sensor type
Interrupted air switch enable Read Only
IAS start check enable
LCI enable
PII enable
Flame threshold
Absolute max fan speed
Absolute min fan speed
PWM frequency
Pulses per revolution
Fan speed up ramp
Fan slow down ramp
Fan gain up
Fan gain down
Customer
Choice - Hidden,
Read Only or
Password
protected
Minimum Range
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Hidden
Read Only
Hidden
Read Only
Read Only
Read Only
2
Read Only
500
Read Only
500
Read Only
Read Only
1
Read Only
Read Only
Read Only
Read Only
Default Setting
50
50
0
1m 0s
A:Internal ignition
(spark)
A:Blower motor
A:On throughout
PFEP
A:Interrupted (off
during Run)
A:No flame sensor
B:Prove via HFS
terminal
B:Prove via LFS
terminal
0m 30s
0m 0s
C:10 seconds
C:10 seconds
0m 10s
0m 15s
Disabled
A:Lockout
A:Lockout
A:Number of
retries not set
5m 0s
A:Lockout
A:Lockout
Disabled
A:10K dual safety
A:no IAS
Enabled
Enabled
Enabled
8
5000
800
D:3000 Hz
3
0
0
50
50
101
Maximum Range Parameter Units
400
400
400
mmm:ss
mmm:ss
mmm:ss
mmm:ss
mmm:ss
mmm:ss
140
.1 Volts/uA
7000
RPM
5000
RPM
10
RPM/sec
RPM/sec
100
100
CB FALCON
750-265