Lead Lag Slave Configuration
Parameters (Hydronic Control Only)
Table 33 displays Lead Lag Slave Configuration parameters.
Fig. 57. Lead Lag slave configuration.
Table 33. Lead Lag Slave
Configuration Parameters.
Parameter
Slave enable
Slave
ModBUS slave
Disabled
Slave mode
Use first
Use last
Equalize run time
Base load rate
0–6000 rpm
Slave sequence
0–8
order
Demand to firing
___hour ___min ___sec
delay
Fan rate during off
0–12000 rpm
cycle
ModBus port
MB1
MB2
No port
ModBus address
0–250
Lead Lag Master Configuration
Parameters (Hydronic Control Only)
Table 34 displays Lead Lag Master Configuration parameters.
Click the Advanced Settings button to see available advanced
parameters as shown in Table 34–43.
CB-8462
Comment
28
Use the left and right arrows to switch between Modulation,
CH, DHW, Frost Protection, Warm Weather Shutdown,
Algorithms, Rate Allocation, Add stage and Drop stage
parameters.
Fig. 58. Lead Lag master configuration and Advanced
Settings button.
Table 34. Lead Lag Master Configuration Parameters.
Parameter
Master enable
Enabled
Disabled
CH setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
CH time of day
-40 °F to 266 °F (-40 °C to 130 °C)
setpoint
ModBus port
MB1
MB2
No port
ModBus address
1–250
Table 35. Lead Lag Master Configuration
Advanced Settings: Modulation Parameters.
Parameter
Modulation backup
Lead outlet sensor
sensor
Slave outlet sensor average
Disabled
Off hysteresis
0 °F to 234 °F
(-17 °C to 112 °C)
On hysteresis
0 °F to 234 °F
(-17 °C to 112 °C)
Hysteresis step time ___Hour ____Minute _____Second
P gain
0 - 400
I gain
0 - 400
D gain
0 - 400
Comment
Comment