CleaverBrooks CFC Operation, Service & Parts Manual page 299

Condensing boiler
Table of Contents

Advertisement

Fig. 80. Setup page.
Press the Display Setup page to display various options that
can be set by the user (see Fig. 81 to Fig. 85)
The General tab (Fig. 81) contains the following settings:
• Display alerts on Status Summary Bar? This determines
whether non-safety alerts will be shown on the summary
bar of the home page
• Display empty parameter groups? This cleans up the
home page by hiding unused parameter groups
• Sound audio alarm for faults? This uses the display
speaker to sound an alarm on shutdown for Falcon faults
Fig. 81. Setup page - General setup.
The COM1 tab (see Fig. 82) contains the following setting:
• Enable COM1 port: This box must be selected to enables
the COM1 interface
• Modbus address range 1-N: Sets the Modbus address for
the connected device (range is 1 to 250).
• Modbus baud rate: Select the baud rate (38400, 19200 or
9600 bps)
The COM2 is Modbus gateway for Building Automation
System (BAS) networking:
• Enable COM2 port: This box must be selected to enables
the COM2 BAS interface
• Modbus address range 1-N: Sets the Modbus address for
the connected device (range is 1 to 250).
• Modbus baud rate: Select the baud rate (38400, 19200 or
9600 bps)
Fig. 82. Setup page - Com ports setup.
Fig. 83. Setup page - Gateway setup.
Fig. 84. Setup page - Screen setup.