CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
000F
0015
0010
0016
0011
0017
0012
0018
0013
0019
0014
0020
0015
0021
0016
0022
0017
0023
0018-001F 0024-0031 RESERVED
0020
0032
0021
0033
0022
0034
0023
0035
4-20 mA remote control
input (S2) terminal
Active CH setpoint
Active DHW setpoint
Active LL setpoint
Register Access Status
Steam pressure
Analog modulation input
Active CH pressure setpoint R
Extended Status Change
BURNER CONTROL
STATUS
Burner control status
Burner control state
Lockout code
Alarm reason
R
U16
4-20 mA (0.1 mA precision) or other (see register 609)
R
U16
-40°-130° (0.1°C precision)
Setpoint determined by CH setpoint source (register 65).
R
U16
-40°-130° (0.1°C precision)
DHW setpoint source (register 81).
R
U16
-40°-130° (0.1°C precision)
setpoint source (register 161).
RR
U16U1
Register data write access status:
6
0=No register writes allowed,
1=Installer register writes allowed,
2=OEM register writes allowed.
3=All register writes allowed.
R
U16
0-150 psi (0.1 psi precision)
R
U16
0=No signal, otherwise
4-20 mA (0.1 mA precision)
Duplicate of register 15 when S2 terminal is 4-20 mA.
U16
0-150psi (0.1psi precision)
R
U16
Register is cleared (all bits zeroed) after read. Identifies
register groups that have new status or configuration
data in them.
Bit map:
15-5=Reserved
4= DHW plate heat exchanger configuration
3=DHW plate heat exchanger status
2-0=Reserved
R
U16
0=Disabled,
1=Locked out,
2-3=Reserved,
4=Anti-short cycle,
5=Unconfigured safety data,
6-33=Reserved,
34=Standby Hold,
35=Standby Delay,
36-47=Reserved,
48=Normal Standby,
49=Preparing,
50=Ignition,
51=Firing,
52=Postpurge,
53-65535=Reserved
R
U16
Burner control sequence (I/O) state (see table 11). Model
type determined by register 176.
R
U16
0=No lockout,
1-4096 (see Table 8)
R
U16
0=None,
1=Lockout (see Lockout code, register 34),
2=Alert (see Table 10),
3=Other
6
a
a
Setpoint determined by
a
Setpoint determined by LL