Stack Sizing; Stack Design Using Room Air For Combustion - CleaverBrooks CFC Operation, Service & Parts Manual

Condensing boiler
Table of Contents

Advertisement

Section 3 — Stack and Intake Vent Sizing and Installation
Table 3-1 STACK DESIGN (SINGLE BOILER) USING ROOM AIR
Boiler Stack/Flue
Boiler
Connection
CFC 500
6" Standard
CFC 750
6" Standard
CFC1000
6" Option
CFC1000
8" Standard
CFC1000
10" Option
CFC1500
8" Option
CFC1500
10" Standard
CFC1500
12" Option
CFC1800
10" Option
CFC1800
12" Standard
CFC 2500
12" Standard
CFC3300
12" Standard
CFC3300
14" Option
* Each additional 90 elbow equals 5 equivalent feet of ductwork. Flue terminations may add 5-10 feet
to the equivalent length and should also be included in the equivalent length calculation.
** Increasing the diameter of the air intake will reduce the overall pressure drop and thereby allow
longer total vent lengths.
Draft tolerance at boiler flue connection during operation is +/- 0.25" WC.
3-10
F. STACK SIZING

1. Stack design using room air for combustion

Boiler
Maximum length of
Flue/Stack
Flue Gas Vent in
Size
Feet*
6"
80
6"
60
6"
80
8"
140
10"
200
8"
60
10"
80
12"
120
10"
60
12"
100
12"
110
12"
60
14"
110
Room
Flue Connection
Combustion Air
Part No.
Required (CFM)
039-01704
125
039-01704
190
039-01646
250
039-01647
250
039-01705
250
039-01645
375
375
039-01644
039-01688
375
039-01644
450
039-01688
450
039-01688
625
039-01761
800
039-01762
800
Air Filter Kit No.
(optional)
880-01858
880-01858
880-01858
880-01858
880-01858
880-02005
880-02005
880-02005
880-02005
880-02005
880-02005
880-02502
880-02502
Part No. 750-263