CleaverBrooks CFC Operation, Service & Parts Manual page 407

Condensing boiler
Table of Contents

Advertisement

Bolded registers are typical boiler/burner status monitoring points.
0084- 0085
0132- 0133
0086- 0087
0134- 0135
0088- 0089
0136- 0137
008A-008B
0138- 0139
008C- 008D
0140- 0141
008E-008F
0142-0143
0090- 0091
0144- 0145
00B1
0177
00B2
0178
00B3
0179
00B4
0180
00B6
0182
00B7
0183
00B8
0184
00C1
0193
00C2
0194
00C3
0195
00C4
0196
00C5
0197
00C6
0198
00C7
0199
00C8
0200
00C9
0201
00CA
0202
00CB
0203
00CC
0204
00CD
0205
00D0
0208
00D3
0211
00D4
0212
00D5
0213
00D6
0214
00D7
0215
01C0
0448
01C5
0453
01C6
0454
01C7
0455
01C8
0456
01D0
0464
01D3
0467
01D7
0471
01DB
0475
CH pump cycle count
R
DHW pump cycle count
R
System pump cycle count
R
Boiler pump cycle count
R
Auxiliary pump cycle count
R
Controller cycle count
R
Controller run time
R
SYSTEM CONFIGURA-
TION
Password
W
Temperature units
R
Antishort cycle time
R
Alarm silence time
R
Reset and restart
W
Burner name
R
Installation data
R
MODULATION CONFIGU-
RATION
CH maximum modulation
R
rate
DHW maximum modula-
R
tion rate
Minimum modulation rate
R
Prepurge rate
R
Lightoff rate
R
Postpurge rate
R
CH forced rate
R
CH forced rate time
R
DHW forced rate
R
DHW forced rate time
R
Burner switch
R/W
Firing rate control
R
Manual firing rate
R
CH CONFIGURATION
CH enable
R/W
CH setpoint
R/W
CH time of day setpoint
R
CH on hysteresis
R
CH off hysteresis
R
CH outdoor reset enable
R
DHW CONFIGURATION
DHW enable
R/W
DHW setpoint
R/W
DHW time of day setpoint
R
DHW on hysteresis
R
DHW off hysteresis
R
LIMITS CONFIGURATION
Outlet high limit setpoint
R
Stack limit setpoint
R
Delta-T inlet/outlet degrees
R
DHW high limit setpoint
R
OUTDOOR RESET (ODR)
CONFIGURATION
U32
0-999,999
U32
0-999,999
U32
0-999,999
U32
0-999,999
U32
0-999,999
U32
0-999,999
U32
Hours
Variable length password string (up to 20 characters) request-
ing ICP permission to write registers.
U16
Display format for temperature at user interface: 0=°F (Fahr-
enheit), 1=°C (Celsius)
U16
0-28800 seconds (8 hours), 0xFFFF=Not configured
U16
0-600 minutes
U16
Successful login required before request is granted. Force soft
reset of ICP subsystems:
0=None,
1=Burner control,
2=Application,
3=Burner control & application,
4=Clear alert log
Variable length string (up to 20 characters)
Variable length string (up to 20 characters)
U16
RPM or %
U16
RPM or %
U16
RPM or %
U16
SAFETY parameter: RPM or %
U16
SAFETY parameter: RPM or %
U16
SAFETY parameter: RPM or %
U16
RPM or %
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
RPM or %
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
0=Off, 1=On. Used to enable/disable burner control.
U16
0=Auto, 1=Manual in Run, 2=Manual in Run&Standby
U16
Firing rate used when control is set to manual (% or RPM)
U16
0=Disable Central Heating, 1=Enable Central Heating
U16
-40°-130° (0.1°C precision)
U16
-40°-130° (0.1°C precision) Setpoint when Time Of Day
switch is on.
U16
0°-130° (0.1°C precision)
U16
0°-130° (0.1°C precision)
U16
0=Disable outdoor reset, 1=Enable outdoor reset
U16
0=DHW disabled, 1=DHW enabled
U16
-40°-130° (0.1°C precision)
U16
-40°-130° (0.1°C precision) Setpoint when Time Of Day
switch is on.
U16
0°-130° (0.1°C precision)
U16
0°-130° (0.1°C precision)
U16
SAFETY parameter: -40°-130° (0.1°C precision)
U16
SAFETY parameter: -40°-130° (0.1°C precision)
U16
Temperature delta between inlet & outlet sensors when Delta-
T limit occurs: 0°-130° (0.1°C precision)
U16
SAFETY parameter: -40°-130° (0.1°C precision)