Outdoor Reset Parameters (Hydronic Control Only); Domestic Hot Water (Dhw) Configuration Parameters; Steam Configuration Parameters; Outdoor Reset Configuration Parameters - CleaverBrooks CFC Operation, Service & Parts Manual

Condensing boiler
Table of Contents

Advertisement

Table 7. Central Heat Hydronic
Configuration Parameters. (Continued)
Parameter
Time of day setpoint Setpoint when Time Of Day switch is
on. -40 °F to 266 °F (-40 °C to 130 °C)
Off hysteresis
Differential above setpoint when boiler
is turned off.
32 °F to 266 °F (0 °C to 130 °C)
On hysteresis
Differential from setpoint when boiler
is turned on. 32 °F to 266 °F (0 °C to
130 °C)
4 mA water
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
20 mA water
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Modulation sensor
Outlet sensor, Inlet sensor, S5 (J8-11)
Modulation Rate
Local
Sensor
P-gain
Gain applied for the P portion of the
PID equation
0-400
I-gain
Gain applied for the I portion of the
PID equation
0-400
D-gain
Gain applied for the D portion of the
PID equation
0-400
Hysteresis step time Time between hysteresis step
changes: 0-600 seconds (0=Disable
hysteresis stepping)
Table 8. Steam Configuration Parameters
Parameter
Steam enable
Disable/enable steam feature
Steam demand
Sensor and LCI
source
Sensor and Remote Stat
Sensor and Stat Terminal
Sensor Only
Steam pressure
Setpoint for normal modulation
setpoint
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam time of day
Setpoint when TOD switch on
setpoint
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Minimum steam
Establishes setpoint for the 4ma. input.
pressure
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam pressure off
Differential below setpoint when boiler
hysteresis
is turned off
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam pressure on
Differential from setpoint when boiler
hysteresis
is turned on.
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam hysteresis
Time between hysteresis changes 0 to
step time
600 seconds (0=disable)
Comment
Comment
15
Table 8. Steam Configuration Parameters
Parameter
Steam P Gain
Gain applied for the P portion of the
PID equation
0-400
Steam I Gain
Gain applied for the I portion of the PID
Equation - 0-400
Steam D Gain
Gain applied for the D portion of the
PID equation
0-400
Steam 4-20 ma
uses 4-20ma remote control function to
remote control
control either the setpoint or
modulation for Steam
Disable, setpoint, modulation
Outdoor Reset Parameters
(Hydronic Control Only)
Table 9 displays Outdoor Reset configuration parameters.
Pressing the left or right arrow displays Lead Lag, which lists
the same parameters.
Fig. 30. Outdoor reset configuration.
Table 9. Outdoor Reset Configuration Parameters.
Parameter
Maximum outdoor
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Minimum outdoor
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Low water
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Minimum water
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Maximum off point
-40 °F to 266 °F (-40 °C to 130 °C)
Domestic Hot Water (DHW)
Configuration Parameters
(Hydronic Control Only)
Table 10 displays Domestic Hot Water (DHW) configuration
parameters.
Comment
Comment
CB-8462