CleaverBrooks CFC Operation, Service & Parts Manual page 417

Condensing boiler
Table of Contents

Advertisement

Table 4. CB Falcon Modbus register map
0003
0003
0004
0004
0005
0005
0006
0006
0007
0007
0008
0008
0009
0009
000A
0010
000B
0011
000C
0012
000D
0013
000E
0014
Annunciation I/O
Limits
Plug-In Module (PIM)
status
TREND STATUS
Demand source
Outlet (S3S4) or Outlet limit
(S3) sensor
Firing rate
Fan speed
Flame signal
Inlet (S1) sensor
DHW (S6S7) or DHW limit
(S6) sensor
S5 sensor
Stack (S8S9) or Stack limit
(S8) sensor
R
U16
Only applicable when Annunciation is enabled
Bit map:
15-8=Reserved (always 0)
7=Annunciator 8/LFS
6=Annunciator 7/HFS
5=Annunciator 6
4=Annunciator 5
3=Annunciator 4
2=Annunciator 3
1=Annunciator 2
0=Annunciator 1/IAS
R
U16
Bitmap:
15-12=Reserved (always 0)
11=Heat exchanger high limit
10=Exchanger T-rise limit
9=Outlet T-rise limit
8=Inversion inlet/exchanger limit
7=Inversion exchanger/outlet limit
6=Inversion inlet/outlet limit
5=Delta T inlet/exchanger limit
4=Delta T exchanger/outlet limit
3=Delta T inlet/outlet limit
2=Stack limit
1=DHW high limit
0=Outlet high limit
R
U16
Bit map:
15-11=Reserved,
10=OEM alert PCB stored in PIM,
9=OEM range PCB stored in PIM,
8=OEM parameter PCB stored in PIM,
7-3=Reserved (always 0),
2=Valid copyright,
1=Lead/Lag enabled,
0= PIM installed
R
U16
Current demand source:
0=Unknown,
1=No source demand,
2=CH,
3=DHW,
4=Lead Lag slave,
5=Lead Lag master,
6=CH frost protection,
7=DHW frost protection,
8=No demand due to burner switch (register 199) turned
off,
9=DHW storage,
10=Reserved,
11=Warm weather shutdown
R
U16
-40°-130° (0.1°C precision)
R
U16
Actual firing rate (%
R
U16
RPM
R
U16
0.01V or 0.01A precision (0.00-50.00V)
R
U16
-40°-130° (0.1°C precision)
R
U16
-40°-130° (0.1°C precision)
R
U16
-40°-130° (0.1°C precision)
R
U16
-40°-130° (0.1°C precision)
5
CB FALCON MODBUS COMMUNICATION
a
b
c
or RPM
).
a
a
a
a