Fig. 15. Safety parameter confirmation.

Fault/Alarm Handling

Each Falcon control reports to the OI display when a safety
lockout or an Alert occurs.
Safety lockouts are indicated on each configuration page as
an alarm bell symbol. At the status page, the History button
turns red (see Fig. 16). If the 833-5105 is displaying the system
status icons, the control in alarm will turn red (see Fig. 17).
Fig. 16. Lockout condition - Status page.
Fig. 17. Lo ckou t co ndi tion - Home page.
CB-8462
The lockout history can be displayed by pressing on the
History button. The state information about each lockout is
displayed along with the date/time that the lockout occurred
(see Table 2). Current date/time stamp is a display setup
feature.
Table 2. Sola Control Lockout History.
Data
Lockout time
Fault code
Annunciator first out
Description
Burner Lockout/Hold
Burner control state
Sequence time
Cycle
Run Hours
I/O
Annunciator 1-8 states
Fault data
An alert log can be displayed for each control by pressing the
Alert button on the bottom of the history status page. A
description of the alert is displayed along with the time when
the alert occurred (see Table 3).
Table 3. Falcon Control Alert Log.
Data
Alert time
Alert code
Description

History Button

The History button on the Home page serves not only as a
button, but also displays Falcon Control lockouts, holds, and
alerts as they occur. The History button can be selected at any
time, regardless of which type of information is displayed, to
view history information. Pressing the History button displays
a dialog box (see Fig. 18) that allows the user to select the
type of history to view. The user can also silence an audible
alarm generated by the control during a lockout or alert by
alarm condition.
This History dialog box provides an exploded view of the
status information displayed in the History button (the font is
larger). One of the four buttons (OK, Lockouts, Alerts, or
Silence) can be selected. If none of these buttons are
selected the dialog box closes after 30 seconds.
10
Comment
Set by display
Unique code defining which
lockout occurred.
First interlock in limit string
results in a shutdown.
Fault description
Source/reason for lockout/
hold
Burner control state timer at
time of fault
Burner control cycle
Burner control hours
All digital I/O status at time of
fault
All annunciator I/O status at
time of fault
Fault dependent data
Comment
Set by display
Unique code defining which
fault occurred.
Alert description