Alerts - CleaverBrooks CFC Operation, Service & Parts Manual

Condensing boiler
Table of Contents

Advertisement

Code
239
Invalid S2 (J8-6) connector type setting
240
Invalid S5 (J8-11) connector type setting
241
Exchanger sensor not allowed with stack
connector setting
242
Invalid DHW auto detect configuration
243
Invalid UV with spark interference not
compatible with Ignitor on throughout PFEP
244
Internal fault: Safety relay test invalid state
245
Invalid Outlet connector type setting for T-
rise
246
4-20mA cannot be used for both modulation
and setpoint control
247
Invalid ILK bounce detection enable
248
Invalid forced recycle interval
249
STAT cannot be demand source when
Remote Stat is enabled
250
Invalid Fan speed error response
251-255
RESERVED
Table 50. Alerts.
Code
EE Management Faults
0
None (No alert)
1
Alert PCB was restored from factory defaults
2
Safety configuration parameters were restored
3
Configuration parameters were restored from
4
Invalid Factory Invisibility PCB was detected
5
Invalid Factory Range PCB was detected
6
Invalid range PCB record has been dropped
7
EEPROM lockout history was initialized
8
Switched application annunciation data blocks
9
Switched application configuration data blocks
10
Configuration was restored from factory defaults
11
Backup configuration settings was restored from
12
Annunciation configuration was restored from
13
Annunciation configuration was restored from
14
Safety group verification table was restored from
15
Safety group verification table was updated
16
Invalid Parameter PCB was detected
17
Invalid Range PCB was detected
System Parameter Errors
18
Alarm silence time exceeded maximum
19
Invalid safety group verification table was
20
Backdoor Password could not be determined.
21
Invalid safety group verification table was
Table 49. Falcon Lockout and Hold Codes. (Continued)
Description
Description
Recommended Troubleshooting of Lockout Codes
Table 50. Alerts. (Continued)
Code
22
CRC errors were found in application
23
Backup Alert PCB was restored from active one
24
RESERVED
25
Lead Lag operation switch was turned OFF
26
Lead Lag operation switch was turned ON
27
Safety processor was reset
28
Application processor was reset
29
Burner switch was turned OFF
30
Burner switch was turned ON
31
Program Module (PM) was inserted into socket
32
Program Module (PM) was removed from socket
33
Alert PCB was configured
34
Parameter PCB was configured
35
Range PCB was configured
36
Program Module (PM) incompatible with product
37
Program Module application parameter revision
38
Program Module safety parameter revision
39
PCB incompatible with product contained in
40
Parameter PCB in Program Module is too large
41
Range PCB in Program Module was too large for
42
Alert PCB in Program Module was too large for
43
IAS start check was forced on due to IAS
System Operation Faults
44
Low voltage was detected in safety processor
45
High line frequency occurred
113
CB FALCON
NOTE
L
L
L
L
L
L
L
L
L
L
L
L
Description
750-265