Procedures For Isolating Cru Problems; Isolating A Power Supply Problem - IBM TS3100 Setup, Operator, And Service Manual

Ibm system storage tape library
Table of Contents

Advertisement

prism sensor/emitter is inoperable, initialization and/or inventory functions can
take a prolonged amount of time to complete due to the lengthy retry recovery
procedure.
If the library is taking an extended amount of time to initialize, to perform an
inventory or even move a cartridge within the library, the magazines prism
integrity should be verified prior to exchanging a library component. This situation
can be noted by the ACTIVITY line on the Operator Panel posting Recovery. Prism
integrity verification can be done by releasing the magazines and inspecting the
cell prisms. Normal initialization or inventory time for a 2U library once the picker
mechanism starts its operation should be approximately 1 to 2 minutes. For a 4U
library, 2 to 3 minutes. A single missing or damaged prism can add 1 to 2 minutes.
If the accessor tray sensor/emitter is inoperable, or several prisms are missing or
damaged, initialization or inventory could exceed 30 minutes or longer. Refer to
Troubleshooting table "Cartridge Movement Problems".

Procedures for Isolating CRU Problems

Isolating a Power Supply Problem

Note: Not all power supplies have LEDs. The original power supply for the 2U
1
2
3
Figure 7-1. A 250w power supply with LEDs
7-8
TS3100 Tape Library and TS3200 Tape Library Setup, Operator, and Service Guide
library did not have LEDs though any power supplies replaced will likely
have LEDs. The 4U library has power supplies with LEDs.
4
6
5