8. Troubleshooting
Code Faults
SYST.SENS.FAIL. SCU
D07
D09
DHW S.FAILURE
D11
ROOM S.A FAIL.
D12
ROOM S.B FAIL.
D13
ROOM S.C FAIL.
D14
MC COM.FAIL
D15
ST.TANK S.FAIL
122
Cause
Description
of the
fault
System sensor fault
SCU
Domestic hot water sensor fault
Remarks:
Heating of domestic hot water is no
longer ensured.
The load pump operates.
The tank load temperature is equal to the
temperature of the inside module.
SCU
A room temperature sensor fault
B room temperature sensor fault
C room temperature sensor fault
Note:
The circuit concerned operates without
any influence from the room sensor.
SCU
Break in communication between the
SCU PCB and the radio module
SCU
Storage tank sensor fault
Note:
The hot water storage tank reheating
operation is no longer assured.
AWHP-2 MIT-IN-2 iSystem
Checking / solution
Bad connection
Check whether the sensor is connected:
4
¼See chapter: "Deletion of
sensors from the memory in the
PCB", page 124
Check the link and the connectors
4
Check that the sensor has been correctly
4
fitted
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
Bad connection
Check whether the sensor is connected:
4
¼See chapter: "Deletion of
sensors from the memory in the
PCB", page 124
Check the link and the connectors
4
Check that the sensor has been correctly
4
fitted
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
Bad connection
Check whether the sensor is connected:
4
¼See chapter: "Deletion of
sensors from the memory in the
PCB", page 124
Check the link and the connectors
4
Check that the sensor has been correctly
4
fitted
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
Bad connection
Check the link and the connectors
4
Boiler module failure
Change the boiler module
4
Bad connection
Check whether the sensor is connected:
4
¼See chapter: "Deletion of
sensors from the memory in the
PCB", page 124
Check the link and the connectors
4
Check that the sensor has been correctly
4
fitted
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
25/06/2014 - 7616371-001-04