AWHP-2 MIT-IN-2 iSystem
Code Messages
B09
BL.SC.IN.OPEN
B10
BL.GROUP.EXT.
B11
BL.COM SCU
B12
BL.WATER MIS.
B13
BL.DHW. S.
B14
BL.OUTSIDE.S
B17
BL.BAD PSU
B18
BL.BAD PSU
B19
BL.NO CONFIG
B39
BL.FLOW
B40
BL.FLOW.STOP
B41
BL.COM.CPT.kWh
B50
BL.S.DEP.CPT.kWh
B51
BL.S.RET.CPT.kWh
B52
BL.CPT.kWh.ELEC1
B53
BL.CPT.kWh.ELEC2
B54
BL.CPT.kWh.THERM
B55
BL.FLOW
25/06/2014 - 7616371-001-04
Description
The BL inlet on the PCU PCB
terminal block is open.
Antifreeze protection.
Failure outside unit.
Communication error with the
SCU PCB.
The water pressure is lower than
0,5 bar
The DHW tank sensor is
disconnected or short circuited
The outside temperature sensor
is disconnected or short
circuited.
The parameters saved on the
PCU PCB are impaired.
The PSU PCB is not recognised Wrong PSU PCB for this heat pump.
The inside module has not been
configured.
Low flow rate.
Flow rate fault.
Communication error with the
energy meter option PCB.
Energy meter flow sensor error. 4
Energy meter return sensor
error.
Electical meter ELEC 1 error.
Electical meter ELEC 2 error.
Thermal meter error.
Low flow rate.
Checking / solution
The contact connected to the BL inlet is open.
Check the contact on the BL inlet.
4
Parameter error.
Check the parameter E. BL
4
Bad connection.
Check the wiring.
4
Consult the error codes specific to the outdoor module.
4
Bad connection
Check the wiring
4
PCB SCU not installed in the equipment
Install an SCU PCB
4
Not enough water in the circuit.
Top up the installation with water.
4
Check that the sensor is actually connected to the
4
S.ECS inlet on the PCU
Check the wiring
4
Check the Ohmic value of the sensor. Replace it if
4
necessary
¼ "Sensor characteristics", page 16
See:
Check that the sensor is actually connected to the
4
S.EXT inlet on the PCU
Check the wiring
4
Check the Ohmic value of the sensor. Replace it if
4
necessary
¼ "Sensor characteristics", page 16
See:
Parameter error on the PCU PCB.
Replace the PCU PCB.
4
Replace the PSU PCB.
4
The PCU PCB has been changed.
Set the type of generator again in the menu
4
#CONFIGURATION (Refer to the original rating plate).
Check the settings of the heating pump on the heat
4
pump.
Check that the filter is not blocked.
4
Check the settings of the heating pump on the heat
4
pump.
Check that the filter is not blocked.
4
Bad connection
Check the wiring
4
Check the connection and resistance of the sensor
Check the connection and resistance of the sensor
4
Check that there is no short-circuit on input ELEC1
4
Check that there is no short-circuit on input ELEC2
4
Check that there is no short-circuit on input THERM
4
Check the settings of the heating pump on the heat
4
pump.
Check that the filter is not blocked.
4
8. Troubleshooting
.
.
119