5. Commissioning
Installer level - Menu #NETWORK
Parameter
(4)
FUNCT
(5)
PARALLEL.CASC
(3)
TIMER GENE P.CASC
(3)
INTER STAGE TIMER
(6)
SLAVE NUMBER
(7)
VM NUMBER
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
(2) The parameter is only displayed if CASCADE is set to NO
(3) The parameter is only displayed if CASCADE is set to ON
(4) The parameter is only displayed if MASTER CONTROLER is set to ON
(5) The parameter is only displayed if FUNCT is set to PARALLEL
(6) The parameter is only displayed if MASTER CONTROLER is set to OFF
(7) According to the configuration
User level - Menu #SETTING
Parameter
Adjustment range Description
(1)
AUTO / 1 ... 10
PERMUT
(1) The parameter is only displayed if CASCADE is on ON and MASTER CONTROLER on ON
0
2
4
6
8
10
12
14
CASCADE
MASTER CONTROLER
E
1
SYSTEM NETWORK
2
FUNCT
1
D
2
INTER STAGE TIMER
#
F

!
% $
AUTO
J
I
STD
110
(1)
Adjustment range Description
Operation in cascade: Successive
TRADITIONAL
tripping of the various generators in the
cascade according to needs
Functioning in parallel cascade: If the
PARALLEL
outside temperature is lower than the
PARALLEL.CASC value, all generators
are started up at the same time
-10 to 20 °C
Outside temperature triggering all stages
in parallel mode
0 to 30 min
Minimum duration of post-operation of the
generator pump
1 to 60 min
Time delay for starting up or shutting
down generators.
2 to 10
Set the network address of the secondary
generator
20 to 39
Set the module's network address
This parameter is used to set the master boiler.
AUTO: The master boiler switches automatically
4
every 7 days
1 ... 10: The master boiler is always the one
4
defined by this value
16
18
20
22
24
ON
ON
TRADITIONAL
4'
9
<
C002409-C-04
n Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VM iSystem as slaves. Proceed as follows:
1. Set parameter CASCADE to ON.
2. Select SYSTEM NETWORK and press the rotary button to go to
the specific menu.
AWHP-2 MIT-IN-2 iSystem
Factory setting Customer
setting
TRADITIONAL
10 °C
0 mn
4 mn
2
20
Factory setting Customer setting
AUTO
25/06/2014 - 7616371-001-04