Pool Connection - DeDietrich AWHP-2 MIT-IN-2 iSystem Installation And Service Manual

Hide thumbs Also See for AWHP-2 MIT-IN-2 iSystem:
Table of Contents

Advertisement

AWHP-2 MIT-IN-2 iSystem
Settings to be made for this type of installation
Parameters
Access
Installer level
DHW BACKUP
#PRIMARY INSTAL.P menu
Installer level
DHW TYPE
#PRIMARY INSTAL.P menu
MINI COOLING A Installer level
#SECONDARY INSTAL.P menu
MINI COOLING B Installer level
#SECONDARY INSTAL.P menu
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
B
2
1
25/06/2014 - 7616371-001-04
4.11.15.
SCU
TS +
B
A
3
A
Z
E
R
T
Y
Settings to be made See chapter
¼ "Professional settings", page 98
MIT/D.COOL
¼ "Professional settings", page 98
SECONDARY
¼ "Professional settings", page 98
7 °C
¼ "Professional settings", page 98
10 °C

Pool connection

0-10V
S AMB C
S AMB B
S AMB A
+ -
4 3 2 1 2 1
2 1
2 1
S SYST + TA -
S ECS
S EXT S DEP C
S DEP B
4
2 1
2 1
2 1
2 1
2 1
2 1
5
Connect the secondary swimming pool pump.
Connect the swimming pool sensor.
Plate heat exchanger.
Pool heating cut-off control
When the parameter I.TEL is on 0/1 B, the
swimming pool is no longer heated when the
contact is open (factory setting), only the
antifreeze continues to be active.
The contact direction can still be adjusted by the
parameter CT.TEL.
Connect the primary swimming pool pump.
Do not connect anything to the terminal block.
PCU
M002712-B
4. Installation
6
61