3 COMMON PARAMETERS
Multiple CPU Settings (Motion CPU) in MT Developer
Multiple PLC Setting (PLC CPU setting) in GX Developer
(a) Multiple CPU settings
Set the following items identically in Multiple CPU Settings (Motion CPU) in
MT Developer and in Multiple CPU Settings (PLC CPU) in GX Developer.
• Number of CPU modules (Included CPU empty slots)
• Operation mode when a CPU stop error occurred
• Multiple CPU high speed transmission area setting (Must be set the same
for all CPUs)
• Multiple CPU synchronous startup setting
3 - 6
Number of CPU
modules
Error operation mode
at the stop of CPU
Multiple CPU high
speed transmission
area setting
Multiple CPU
synchronous startup
setting
Select tab "Multiple
CPU high speed
communication area
setting"
Set "Use multiple
CPU high speed
communication".