Removing the FANBP (Rear of M9000)
FIGURE 20-18
10. Place the removed BP on an antistatic mat.
11. Mount the replacement BP by following the removal instructions in
in reverse order.
Note – To mount a FAN BP on a fan shelf that has a guide pin, align the FAN BP with the
guide pin during mounting.
Caution – Be sure not to hit connector parts of the BP against anything. Otherwise, the
connection pins may be seriously damaged.
12. Switch on all main line switches for the AC section (ACS) in the power supply
system.
13. Confirm that the XSCF STANDBY LED (green) on the operator panel remains lit.
If it is blinking, wait until it remains lit.
Chapter 20 Backplane Replacement