Fujitsu SPARC Enterprise M8000 Service Manual page 325

Oracle
Hide thumbs Also See for SPARC Enterprise M8000:
Table of Contents

Advertisement

5. Switch off all main line switches for the AC section (ACS) in the power supply
system. (See
Section 4.5.3, "Main Line Switch Locations" on page
Note – If the optional three-phase 200 VAC input power supply unit is installed, the main
line switches are located on the three-phase ACS.
Note – If the dual power feed option is installed, switch off the main line switches for both
power supply units.
Caution – After stopping all the domains, be sure to switch off the main line switches in
the power supply system to completely shut off the supply of power.
6. Connect the clip of the antistatic wrist strap and of the antistatic mat to the server
grounding port. (See
7. Ensure that the metallic underside of the wrist strap is in direct contact with your
skin.
The wrist strap should be snug around the wrist so that it does not rotate. (See
"Antistatic Precautions" on page
Caution – Before handling FRUs, be sure to connect the clip of the antistatic wrist strap
and of the antistatic mat to the server grounding port, and attach the band of the wrist strap
to one of your wrists. Place the FRUs on the grounded antistatic mat. Failure to take these
antistatic measures might result in serious damage.
8. Remove the CD-RW/DVD-RW drive unit to be replaced. (See
)
FIGURE 14-6
a. Using a Phillips screwdriver, loosen the two knob screws securing the
CD-RW/DVD-RW drive unit to be replaced.
b. While grasping the knob screws, pull out the CD-RW/DVD-RW drive unit slowly
from the slot.
9. Place the removed CD-RW/DVD-RW drive unit on an antistatic mat.
Section 1.4, "Antistatic Precautions" on page
1-9)
Chapter 14
CD-RW/DVD-RW Drive Unit Replacement 14-13
4-30)
1-9)
Section 1.4,
or
FIGURE 14-5