Fujitsu SPARC Enterprise M8000 Service Manual page 263

Oracle
Hide thumbs Also See for SPARC Enterprise M8000:
Table of Contents

Advertisement

5. Ensure that the metallic underside of the wrist strap is in direct contact with your
skin.
The wrist strap should be snug around the wrist so that it does not rotate. (See
"Antistatic Precautions" on page
Caution – Before handling FRUs, be sure to connect the clip of the antistatic wrist strap
and of the antistatic mat to the server grounding port, and attach the band of the wrist strap
to one of your wrists. Place the FRUs on the grounded antistatic mat. Failure to take these
antistatic measures might result in serious damage.
6. For the M9000 (with the expansion cabinet), disconnect the cables from all
connectors of the XSCFU to be replaced.
7. Remove the XSCFU to be replaced.
a. If the M9000 server expansion cabinet is installed, slide the cable support bracket
at the front of the XSCF unit up or down by one hole, and then remove the cable
connected to the XSCF unit.
b. Using a Phillips screwdriver, turn the knob screws securing the upper and lower
eject/lock levers (in the M8000 server) or left and right eject/lock levers (in the
M9000 server) 90 to 180 degrees to unlock the levers. (Turn the knob screw while
lightly pulling the lever.)
c. Unlock the eject/lock levers to pull the XSCFU off the backplane.
d. While grasping the eject/lock levers, pull out the XSCFU slowly from the slot.
1-9)
Chapter 11
Section 1.4,
XSCF Unit Replacement
11-7