J Output
F Output
assignments
The E5EK-DRT supports the following four outputs.
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
When using control outputs 1 and 2, set the output unit (sold sepa-
rately). Nine output units are available to suit the output circuit config-
uration.
Note: The output functions of the E5EK-DRT do not operate for five
seconds after the E5EK-DRT is turned ON.
The E5EK-DRT supports the following ten output functions.
Control output (heat)
Control output (cool)
Alarms 1 to 3
HBA
LBA
Error 1 (input error)
Error 2 (A/D converter error)
Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2,
auxiliary output 1, and auxiliary output 2.
There are restrictions on how assignment destinations (control output
1, control output 2, auxiliary output 1, and auxiliary output 2) can be
used. For details, see 3.3 Setting Output Specifications.
In the example on the previous page, "control output (heat)" is assigned
to "control output 1", "alarm 1" is assigned to "control output 2",
"alarm 2" is assigned to "auxiliary output 1", and "alarm 3" is assigned
to "auxiliary output 2". Accordingly, the configuration is such that heat-
ing control output is connected to control output 1, and alarm output is
connected to control output 2 and auxiliary outputs 1 and 2.
Control outputs 1 and 2 are used depending on the differences in con-
trol method as follows.
Control Method
Standard control
Heating and cooling
control
Control Output 1/
Control Output 2
Control output (heat)/Alarm, etc.,.
Control output (heat) /
Control output (cool)
1.2 Input and Output
1--5