HBA latch
• When this parameter is set to ON, the heater burnout alarm is held until either of
the following conditions is satisfied:
a The heater burnout set value is set to "0.0A".
Function
b The controller's power OFF is turned OFF then back ON again.
[
Comment
F Related article
4.4 How to Use the Heater Burnout Alarm (page 4-9)
F Related parameters
See
"Control output assignment 1" "Control output assignment 2" "Auxiliary output
assignments 1" "Auxiliary output assignments 2" (setup mode)
Remote SP enable
• When this parameter is set to "ON", the remote SP and local SP can be switched
for use. (That is, to the SP mode can be specified.) Also, the "set point during SP
ramp" parameter is enabled at all times.
Function
• When this parameter is set to "OFF", only the local SP can be used. The set point
during SP ramp is enabled only when the SP ramp function is enabled.
[
Comment
F Related article
4.3 How to Use the Remote SP (page 4-7)
F Relate parameters
See
"Set point during SP ramp" (level 0 mode)
"SP mode" (level 2 mode)
Setting Range
]: Enabled/[
]: Disabled
Setting Range
]: Enabled/[
]: Disabled
Conditions of Use
The HBA output function must be
assigned.
Default
[
]
Default
[
]
Option Mode
5--39