F Calibration :
0 to 10VDC
(1) When [
] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the
key. The display changes to [
tion display). Set the STV output to 10VDC. When the value on the
No.2 display has stabilized (changes of several digits max.), press
the
key to temporarily store the calibration data.
(3) Press the
key. The display changes to [
display). Set the STV output to 0V . When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(4) Press the
key until the display changes to the data save dis-
play. Press the
two seconds later the calibration data is saved to internal memory.
If you press the
calibration data is invalidated.
(5) This completes calibration of voltage input (0 to 10VDC). Press the
key to return the display to [
7.5 Calibrating Voltage Input
key. The No.2 display changes to [
key when the No.2 display reads [
].
] (10VDC calibra-
] (0V calibration
], and
], the
7--11