J Setting range and Indication range of Sensor input
Input
JPt100
Pt100
Pt100
K
K
J
J
T
E
L
L
U
N
R
S
B
W
PLII
4 to 20mA
0 to 20mA
1 to 5VDC
0 to 5VDC
0 to 10VDC
J Output Rating
and Performance
A--4
Setting Range
-199.9 to 650.0(_C)
/-199.9 to 999.9(_F)
-199.9 to 650.0(_C)
/-199.9 to 999.9(_F)
-100.0 to 100.0(_C)
/-150.0 to 250.0(_F)
-200 to 1300(_C)
/-300 to 2300(_F)
0.0 to 500.0(_C)
/0.0 to 900.0(_F)
-100 to 850(_C)
/-100 to 1500(_F)
0.0 to 400.0(_C)
/0.0 to 750.0(_F)
-199.9 to 400.0(_C)
/-199.9 to 700.0(_F)
0 to 600(_C)
/0 to 1100(_F)
-100 to 850(_C)
/-100 to 1500(_F)
0.0 to 400.0(_C)
/0.0 to 750.0(_F)
-199.9 to 400.0(_C)
/-199.9 to 700.0(_F)
-200 to 1300(_C)
/-300 to 2300(_F)
0 to 1700(_C)
/0 to 3000(_F)
0 to 1700(_C)
/0 to 3000(_F)
100 to 1800(_C)
/300 to 3200(_F)
0 to 2300(_C)
/0 to 4100(_F)
0 to 1300(_C)
/0 to 2300(_F)
One of following ranges depending on
results of scaling
-1999 to 9999
-199.9 to 999.9
-19.99 to 99.99
-1.999 to 9.999
The standard applicable to each input type are as follows:
K, J, T, E, R, S, B :
L
: Fe-CuNi, DIN 43710-1985
U
: Cu-CuNi, DIN 43710-1985
N
: Nicrosi 1-NisiL, IEC584-1; 1977 Amendment No.1; 1989
W
: W5Re/W26Re, ASTM E988-1990
PLII
: According to the PLATINEL II Electromotive Force Tables
from ENGELHARD
Jpt100 : JIS C 1604-1989, JIS C 1606-1989
Pt100 : IEC751 ; 1983
These are according to the output unit mounted. For details on output
unit ratings, see page 2-8.
Indication Range
-199.9 to 735.0(_C)
/-199.9 to 999.9(_F)
-199.9 to 735.0(_C)
/-199.9 to 999.9(_F)
-120.0 to 120.0(_C)
/-190.0 to 290.0(_F)
-350 to 1450(_C)
/-560 to 2560(_F)
-50.0 to 550.0(_C)
/-90.0 to 990.0(_F)
-195 to 945(_C)
/-260 to 1660(_F)
-40.0 to 440.0(_C)
/-75.0 to 825.0(_F)
-199.9 to 460.0(_C)
/-199.9 to 790.0(_F)
-60 to 660(_C)
/-110 to 1210(_F)
-195 to 945(_C)
/-260 to 1660(_F)
-40.0 to 440.0(_C)
/-75.0 to 825.0(_F)
-199.9 to 460.0(_C)
/-199.9 to 790.0(_F)
-350 to 1450(_C)
/-560 to 2560(_F)
-170 to 1870(_C)
/-300 to 3300(_F)
-170 to 1870(_C)
/-300 to 3300(_F)
-70 to 1970(_C)
/10 to 3490(_F)
-230 to 2530(_C)
/-410 to 4510(_F)
-130 to 1430(_C)
/-230 to 2530(_F)
-10 to 110% of setting range. Note, however
that max. value is -1999 to 9999
IEC 584-1 ; 1977
Conventional
indication
JPt100
Pt100
K1
K2
J1
J2
T
E
L1
L2
U
N
R
S
B
W
PLII

Advertisement