Omron E5EK DEVICENET User Manual page 85

Digital controller compobus/d (devicenet) type
Table of Contents

Advertisement

_C/_F selection
• This parameter can be used when thermocouple or platinum resistance thermom-
eter is selected as the input type.
• Set the temperature input unit to either of "_C" or "_F".
Function
Comment
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
See
"Input type" (setup mode)
Control output 1
assignment
Control output 2
assignment
• Assigns the output functions to either of control output 1 or 2.
• The following seven output functions can be assigned as outputs:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, and LBA.
Function
• Errors 1, 2 and 3 cannot be assigned as outputs.
• When the output function assigned to control output 1 or control output 2 is ON, the
"OUT1" or "OUT2" LED lights. However, note that the LED does not light when
control output (heat) or control output (cool) are assigned to linear outputs such as
current and voltage.
• When the output function assigned to control output 2 is ON, the "OUT2" LED
lights.
Symbol
Function
Comment
Defaults:
"Control output 1" = [
F Related article
3.3 Setting Output Specifications (page 3-7)
F Related parameters
See
• Alarm-related parameters
• Heating and cooling related parameter
"LBA detection time" (level 2 mode)
Setting Range
: _C /
: _F
Control output
(heat)
Conditions of Use
The input type must be set to tempera-
ture input (thermocouple or platinum
resistance thermometer).
Default
Conditions of Use
The control must be standard control or
heating and cooling control.
Control output
Alarm 1 Alarm 2 Alarm 3
(cool)
], "Control output 2" = [
Setup Mode
HBA
LBA
]
5--27

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ek-drtE5ek