MV upper limit
MV lower limit
MV change rate limit
• The "MV upper limit" and "MV lower limit" parameters set the upper and lower
limits of the manipulated variable. When the manipulated variable calculated by
the E5EK-DRT controller is outside of the upper-and lower-limit range, the upper
Function
limit or lower limit set to these parameters is output, respectively.
• The "MV change rate limit" parameter sets the maximum permissible change
width per second of the manipulated variable. If a change in the manipulated vari-
able causes this parameter setting to be exceeded, the calculated value is reached
while changing the value by the per-second value set in this parameter.
This function is disabled when the set value is "0.0".
• MV upper limit
The setting ranges during standard control and heating and cooling control are
different. Also, the manipulated variable at the cooling side during heating and
Comment
cooling control is expressed as a negative value.
Control Method
Standard
Heating and cooling
• MV lower limit
The setting ranges during standard control and heating and cooling control are
different. Also, the manipulated variable at the cooling side during heating and
cooling control is expressed as a negative value.
Control Method
Standard
Heating and cooling
• MV change rate limit
Setting Range
0.0 to 100.0
F Related article
4.2 Operating Condition Restrictions/Manipulated variable restrictions (page 4-4)
See
Conditions of Use
The control must be 2-PID control
Setting Range
MV lower limit +0.1 to 105.0
0.0 to 105.0
Setting Range
-5.0 to MV upper limit -0.1
-105.0 to 0.0
Unit
Default
%/S
0.0
Level 2 Mode
Unit
Default
%
105.0
%
105.0
Unit
Default
%
-5.0
%
-105.0
5--21