Omron E5EK DEVICENET User Manual page 69

Digital controller compobus/d (devicenet) type
Table of Contents

Advertisement

AT Execute/Cancel
• Selects the limit cycle of MV change width (40% or 100%) for execution. After AT
execution, the "PID" and the "LBA detection time" (LBA: Loop Break Alarm)
parameters are set automatically.
Function
• During heating and cooling control, only 100%AT can be executed.
• When this parameter is selected, the setting becomes [
• To execute 40%AT, select [
execution of auto-tuning, the AT LED flashes. However, note that during heating
Example
and cooling control, [
of use
• When AT execution ends, the parameter setting automatically returns to [
F Related article
3.7 Adjusting Control Operation (page 3-15)
F Related parameters
See
"Run/Stop" (level 0 mode)
"Proportional band" "Integral time" "Derivative time" (level 1 mode)
"LBA detection time" (level 2 mode)
Alarm value 1
Alarm value 2
Alarm value 3
• This parameter is used for monitoring or changing the alarm values of alarm outputs
1 to 3.
• During temperature input, the decimal point position is dependent on the cur-
Function
rently selected sensor, and during analog input on the results of scaling.
Setting Range
-1999 to 9999
Comment
F Related article
3.4 Setting Alarm Type (page 3-10)
F Related parameters
See
"Input type" "Scaling upper limit" "Scaling lower limit" "Decimal point" "Control
output 1 assignment" "Control output 2 assignment" "Auxiliary output 1 assign-
ment" "Auxiliary output 2 assignment" "Alarm 1 type" "Alarm 2 type" "Alarm 3
type" "Alarm 1 open in alarm" "Alarm 2 open in alarm" "Alarm 3 open in alarm"
(setup mode)
"Alarm 1 hysteresis" "Alarm 2 hysteresis" "Alarm 3 hysteresis" (level 2 mode)
"Standby sequence reset method" (expansion mode)
Conditions of Use
The controller must be in operation with
2-PID control.
], and to execute 100%AT, select [
] is not displayed.
Conditions of Use
Alarms must be assigned as outputs.
For example, if alarm outputs 1 and 2
only are assigned as outputs, the "alarm
value 3" parameter cannot be used.
Unit
Default
EU
0
Level 1 Mode
].
]. During
].
5--11